Analysis of Factors Affecting Sub-Synchronous Oscillation in Doubly-Fed Wind Power Grid-Connected System Based on Impedance Sensitivity and Research on Suppression Strategy

ELECTRIC POWER COMPONENTS AND SYSTEMS(2024)

引用 0|浏览0
暂无评分
摘要
Aiming at the matter of sub-synchronous oscillation (SSO) of the doubly-fed induction generator (DFIG) series compensation capacitors grid connection, a SSO suppression strategy based on adding damping controllers in rotor-side converter (RSC) is put forwarded. Considering the control parameters of power and current control loops of RSC, the equivalent impedance model of DFIG series compensation grid connection (SCGC) is established, and then combined with the equivalent RLC resonant circuit of the system, the mechanism and factors of SSO are analyzed by impedance method. Calculating the impedance sensitivity of the system impedance to parameters by sensitivity analysis method, so as to identify the leading factor affecting the SSO characteristics of wind power system. Combined with the stability criterion of system impedance characteristics, the parameters are adjusted to meliorate system stability. Based on the leading factor affecting the SSO and the mechanism of the SSO, the damping controllers are added in the RSC to supply positive damping for the system to eliminate the negative damping brought by the RSC and rotor resistance, thus suppressing the SSO of the system. The validity of the put forwarded suppression strategy is proved through PSCAD/EMTDC simulation.
更多
查看译文
关键词
sub-synchronous oscillation,DFIG,damping controllers,impedance sensitivity,suppression strategy