Particle characterization in commercial buildings: A cross-sectional study in 40 offices in Singapore

Science of The Total Environment(2024)

引用 0|浏览2
暂无评分
摘要
There is a knowledge gap in understanding how existing office buildings are protecting occupants from exposure to particles from both indoor and outdoor sources. We report a cross-sectional study involving weekly measurements of size-resolved indoor and outdoor particle concentrations in forty commercial building offices in Singapore. The outdoor and indoor particles size distributions were single mode with daytime peak number concentrations at 36.5 nm and 48.7 nm. Outdoor concentrations were significantly greater than indoors for all particle diameters. Indoor particle concentrations were generally low due to: 1) relatively high indoor particle removal (IPR) rates; 2) low indoor source strengths; and 3) low indoor particle of outdoor proportion (IPOP). We found that the ventilation system type had a substantial effect on indoor particle levels, IPR and IPOP. Through linear mixed model analyses, we identified dependencies of IPR rates with the use of MERV13 filters in supply air and filter maintenance frequency, IPOP with the use of MERV13 filters in the fresh air and supply air ducts and low particle source strength with regular daily cleaning presumably due to dust reservoir removal. Lastly, the contribution of outdoor sources was mainly seen for ultrafine and fine particles but less pronounced for coarse particles. This study provided detailed understanding of particle exposure in building offices and their influencing factors, facilitating future research on health impact of particle exposures.
更多
查看译文
关键词
Office buildings,Indoor particles,Sources,Indoor particle of outdoor proportion,Indoor particle removal rate,Monitoring
AI 理解论文
溯源树
样例
生成溯源树,研究论文发展脉络
Chat Paper
正在生成论文摘要