Structure Selection and Key Technology of 110kV Oil-immersed Shunt Reactor for Low-voltage Reactive Compensation in AC UHV Substation.

Sustainable Power and Energy Conference(2023)

Cited 0|Views7
No score
Abstract
In special environment areas, such as high altitude or high seismic intensity areas, the dry-type air-core shunt Reactor has relatively poor environmental adaptability, and its use has certain limitations. Oil-immersed shunt reactor for low-voltage reactive compensation in AC UHV substation can be considered. The 110kV oil-immersed shunt reactor required by the UHV project has a certain challenge in design and manufacture due to its three-phase capacity of 240Mvar. Based on the 1000kV UHV AC project from Sichuan to Chongqing, this paper analyzes the feasibility of using 110kV oil-immersed shunt reactor; The single-phase structure and three-phase structure of oil-immersed shunt reactor are compared and analyzed, and the magnetic leakage and local overheating control, vibration and noise control of the product are simulated and analyzed.
More
Translated text
Key words
Ac UHV Substation,110kv Oil-immersed Shunt Reactor,Structure Selection,Key Technology