Chrome Extension
WeChat Mini Program
Use on ChatGLM

Effects of PLL in the Damping Unit of a Gird-Connected VSG

2022 IEEE International Power Electronics and Application Conference and Exposition (PEAC)(2022)

Cited 1|Views18
No score
Abstract
As a promising control method for grid-forming converters, the virtual synchronous generator (VSG) control strategy was developed quickly using different damping units. A straightforward approach is to emulate the dynamics of a synchronous generator (SG), where a phase-locked loop (PLL) is employed to increase the transient damping ratio by measuring the angular frequency of the grid. Ignoring the effects of PLL, this damping method can effectively improve the active power stability of a grid-connected VSG. However, the impact and the mechanism of the introduced PLL are not distinct. Considering the effects of PLL, the dynamic model of a grid-connected VSG is established in this paper. Further investigations reveal that the PLL will introduce a pair of unexpected eigenvalues, which will trigger instability when the bandwidth of the PLL is higher than a critical value. Finally, the theoretical analysis is verified by simulation results.
More
Translated text
Key words
virtual synchronous generator (VSG),phase-locked loop (PLL),stability,damping ratio.
AI Read Science
Must-Reading Tree
Example
Generate MRT to find the research sequence of this paper
Chat Paper
Summary is being generated by the instructions you defined