A General Self-Adaptive DC Current Control of LCC-HVDC for Eliminating Subsequent Commutation Failure

IEEE Transactions on Power Delivery(2023)

引用 1|浏览5
暂无评分
摘要
With more renewable resources are integrated into the receiving-end AC grid through the LCC-HVDC link, a single-infeed LCC-HVDC (SIDC) system is facing a critical subsequent commutation failure (SCF), which stems from the poor dynamic reactive power support capability of the existing LCC-HVDC link's control strategies. This letter proposes a general self-adaptive DC current control (GSDC 2 ) of LCC-HVDC to eliminate the SCF, based on the dynamic reactive power interaction mechanism. Then, multiple comparative studies with the existing control strategies are implemented to verify the validation of the proposed control strategy by PSCAD/EMTDC TM . A fast evaluation index, called general commutation failure immunity index (GCFII), is also defined to show the performance of the proposed control strategy in eliminating the SCF.
更多
查看译文
关键词
Reactive power, Voltage control, Indexes, Current control, Inverters, Power system dynamics, HVDC transmission, LCC-HVDC, DC current control, subsequent commutation failure, commutation failure immunity index