谷歌浏览器插件
订阅小程序
在清言上使用

Diagnosis and Analysis of a 220kV Transformer Winding Deformation Defect

Zhao Liu, Jiao Wang,Xiaolong Tian, Xiaoyan Liu, Xiaoxi Li

2023 5th Asia Energy and Electrical Engineering Symposium (AEEES)(2023)

引用 0|浏览4
暂无评分
摘要
This paper introduces a severe medium voltage winding deformation defect of a 220kV power transformer, which is detected by conducting routine tests. The frequency response analysis (FRA), low-voltage short-circuited impedance test and winding capacitance test is comprehensively employed for the winding deformation diagnosis and positioning. In consideration of the actual short-circuit impacts and the anti- short circuit ability, the transformer is replaced and returned to its factory for further disassembly inspection and maintenance. From the aspects of short-circuit impact statistics, deformation test approaches, coil material control and anti-short circuit ability management, the corresponding technical measures and daily maintenance suggestions are proposed in details to prevent main transformers from short-circuit damage.
更多
查看译文
关键词
transformer,winding deformation,anti-short circuit ability,frequency response analysis