Temperature Dependence of FDR Response for Thermally Aged Low-Voltage Cables

2022 IEEE Conference on Electrical Insulation and Dielectric Phenomena (CEIDP)(2022)

引用 0|浏览3
暂无评分
摘要
Frequency Domain Reflectometry (FDR) has attracted significant attention for use in nuclear power plants (NPPs) for non-destructive cable health monitoring. However, cable aging detection using FDR faces challenges due to its high sensitivity to environmental factors such as temperature, vibrations, proximity to other cables, and so on. This work aims to evaluate the influence of measurement temperature on the FDR reflected signal in a low voltage cable undergoing accelerated thermal aging. A 100 ft long multi-core low-voltage unshielded power cable insulated with flame retardant ethylene propylene rubber (FR-EPR) and covered by a chloro-polyethylene (CPE) jacket was selected for this study. The cable was energized during aging by a 480 V-AC 3-phase motor, and a 30 ft mid-section of this cable was routed through an air circulating oven held at 140 degrees C for up to an effective aging time of 62 days. FDR measurements were taken periodically with the oven on (at 140 degrees C) and with the oven off (at 22 degrees C). A comparative analysis of data collected at both temperatures showed that the FDR response was strongly dependent on measurement temperature. FDR measurements at ambient temperature showed large peaks corresponding to impedance changes in the aged section of the cable after 3 days of aging. These peaks continued to rise steadily with increasing aging time. However, for measurements taken at 140 degrees C, slowly rising peaks in the oven region (aged section) were observed only after a lead time of 23 days of aging. This work highlights the importance of measurement temperature on the performance of FDR as a condition monitoring tool for aging cables.
更多
查看译文
关键词
100 ft long multicore low-voltage,aged section,aging cables,ambient temperature,effective aging time,FDR faces challenges,FDR measurements,FDR response,flame retardant ethylene propylene rubber,low voltage cable,measurement temperature,nondestructive cable health monitoring,nuclear power plants,oven region,temperature dependence,thermal aging,thermally aged low-voltage cables,time 23.0 d,time 3.0 d,time 62.0 d
AI 理解论文
溯源树
样例
生成溯源树,研究论文发展脉络
Chat Paper
正在生成论文摘要