Study on the characteristic components of SF6 decomposition products of gas insulated switchgear inner insulators under abnormal heating

Lijun Fu, Jian Zhang, Lei Wang,Mingchen Gong, Peng Zhang,Shiyu Chen,Jianquan Liang

Seventh International Conference on Electromechanical Control Technology and Transportation (ICECTT 2022)(2022)

引用 0|浏览3
暂无评分
摘要
The abnormal heating test model of GIS internal insulation was established. The abnormal heating test of aluminum-filled basin insulator under steady state current was carried out. The content of SO2, H2S and CO2 remained stable at the beginning of the experiment, and the content of SO2, H2S and CO2 increased obviously when the experiment reached a critical point. The abnormal heating test model of the inner insulator of the gas insulated switchgear was established. The overheat test of solid insulation was carried out under the condition of 0.3 MPa absolute pressure in the gas chamber and without adsorbent. The overheat fault duration was 6 h and the overheat fault temperature was respectively 200℃、250℃, 300℃ and 350℃, the decomposition products of SF6 are CO, CO2, SO2, SOF2, H2S, COS and CF4. The generation mechanism of SF6 decomposition products under abnormal conditions is also analyzed to guide the judgment of internal faults and operation defects of equipment on site and ensure the safe and stable operation of power grid equipment.
更多
查看译文
关键词
switchgear inner insulators,sf6 decomposition products,abnormal heating
AI 理解论文
溯源树
样例
生成溯源树,研究论文发展脉络
Chat Paper
正在生成论文摘要