A Coordinated Multi-Element Current Differential Protection Scheme for Active Distribution Systems
IEEE Transactions on Power Delivery(2022)
摘要
This paper introduces a current differential protection scheme, appropriate for application in medium voltage active distribution systems, where it is desired to keep the greatest possible number of loads and DG units energized during a fault. Conventional two-terminal percentage current differential relays are used to form successive, time-current-coordinated, differential protection zones. Multiple time-delayed differential elements in each protection zone guarantee coordination with the zone's lateral protection devices, as well as between successive differential protection zones. Sensitive time-delayed differential elements protect against relatively high-resistance faults, while instantaneous differential elements minimize protection speed whenever possible. Additional emergency differential elements deal with post-fault topology changes and breaker failure conditions enhancing the overall scheme's performance. The proposed scheme is applied to a model of real medium voltage distribution system with distributed generation, considering a ring topology operation. A detailed simulation-based study proves the applicability and enhanced performance of the proposed scheme.
更多查看译文
关键词
Differential protection,distributed generation,percentage differential relay,power distribution systems,protection coordination