Synchronization Mechanism between Power-Synchronized VS and PLL-Controlled CS and the Resulting Oscillations

IEEE Transactions on Power Systems(2023)

引用 1|浏览1
暂无评分
摘要
Synchronization is the key of AC power system operation, but its mechanism becomes unclear with the large-scale integration of voltage-source converters (VSCs). As an important feature distinguishing VSCs from synchronous generators (SGs), the current-source characteristics of VSCs have hardly been focused from the perspective of synchronization. In this letter, a synchronization mechanism between power synchronized voltage-source (VS) and PLL-controlled current-source (CS) is clarified. Based on this mechanism, negative damping oscillations of SGs caused by VSCs are disclosed.
更多
查看译文
关键词
Current-source (CS),negative damping,oscillations,synchronization mechanism,voltage-source (VS)