Parameters design of voltage sharing components for the series multi-break mechanical switch

IET SCIENCE MEASUREMENT & TECHNOLOGY(2022)

Cited 0|Views4
No score
Abstract
Series multi-break mechanical switch is one of the critical components of high-voltage hybrid DC circuit breakers. However, due to the existence of distributed capacitance, the voltage distribution between the breaks is not balanced. This paper proposed a voltage sharing configuration method of the mechanical switch of hybrid DC circuit breaker, and carried out the static DC voltage and the transient voltage distribution characteristics tests to verify its effectiveness. Considering the influence of whole structure of the circuit breaker, this paper established the electrostatic field model and circuit simulation model of a typical +/- 535-kV hybrid DC circuit breaker. And it analyzed the influence of single break's opening fault, breaking open distance, and the shielding fitting on the voltage distribution characteristics of series six break mechanical switch. According to the simulation results based on the Zhangbei voltage source converter-based high-voltage direct current project type test parameters, the parameters design of the voltage sharing components of the mechanical switch are obtained, which can meet the voltage sharing coefficient requirement of 95%.
More
Translated text
Key words
voltage sharing components
AI Read Science
Must-Reading Tree
Example
Generate MRT to find the research sequence of this paper
Chat Paper
Summary is being generated by the instructions you defined