A novel type of PEMFC-based CCHP system with independent control of refrigeration and dehumidification

APPLIED THERMAL ENGINEERING(2022)

引用 10|浏览10
暂无评分
摘要
The traditional combined cooling, heating and power (CCHP) system can only provide cooling power, heating power and electricity. However, when the CCHP system is used in places with high humidity requirements such as data centers, it cannot meet the humidity control requirements. Based on this, this study proposes a CCHP system with independent control of refrigeration and dehumidification based on a PEMFC. The system model is developed by MATLAB/Simulink, and its performance and efficiency are comparatively analyzed. The results show that the current density and hot water distribution ratio are critical to the performance of the system. Meanwhile, the mass flow rate of the cooling water and chilled water of the adsorption chiller and the parameters of the process air also have an impact on the performance of the system. When the mass flow rates of cooling water and chilled water increase from 0.2 kg.s(-1) to 0.8 kg.s(-1), the cooling power of the system increases from 5.3 kW and 5.12 kW to 6.52 kW and 6.64 kW, respectively. Moreover, the addition of the dehumidification system reduces the cooling power by 1.28 kW but removes the latent heat of the process air by about 1.84 kW.
更多
查看译文
关键词
CCHP,PEMFC,Adsorption chiller,Wheel dehumidification,System performance