Analysis and Application of On-line Monitoring Technique of Partial Discharge for GIS Based on UHF Method

High Voltage Apparatus(2015)

Cited 23|Views0
No score
Abstract
To timely understand insulation state of GIS equipment, on-line monitoring of partial discharge is necessary. According to the existing UHF methods and the analysis on a partial discharge case of a 220 k V substation, the authors propose that by changing the operation mode of GIS equipment and using a variety of testing instruments for integrated diagnosis, the uncertain interferences from instrument itself and external environment can be effectively excluded. Hence the accuracy of partial discharge monitoring and positioning results can be improved. The proposed method may facilitae disassembly processing. Operational experience shows that the UHF partial discharge monitoring system installed on GIS equipment can timely detect hidden troubles to ensure safe and stable operation of the equipment.
More
Translated text
Key words
partial discharge,monitoring,gis,on-line