The nonlinear characteristics of transformer broadband

Journal of Physics: Conference Series(2020)

引用 0|浏览0
暂无评分
摘要
Abstract At present, the modeling of the transformer broadband nonlinear characters is based on the nonlinear features of 50Hz, so there are still some questions. In this paper, the magnetic hysteresis loop of the silicon steel in the the range of 50Hz to 100kHz is measured by using a measuring system composed of a 25cm Epstein square coil and an amh-1m magnetometer. The J-A parameters of the silicon steel core in the frequency wide range of the range of the optimized by using the hybrid means on the oneran fish swarm and L-M. Then, the nonlinear core model of transformer based on J-A parameters is set in PSPICE. Based on the model, the transformer simulation circuit is built. By applying sinusoidal voltage signal of the specific frequency to the nonlinear transformer model with the specific frequency, the non-linear characters of the transformer in wide frequency range areed. It is found the nonlinear characters of the transformer core change dramatically with the change of the frequency. Therefore, in the broadband nonlinear modeling of the transformer, using the nonlinear characters at 50Hz to nonlinear the broadband model will lead to large error. In the follow-up modeling research, scholars should consider the nonlinear characters of the transformer to the set the model, and try to use the nonlinear characters of the transformer under the frequencies for the broadbandlinear modeling.
更多
查看译文
关键词
transformer broadband,nonlinear characteristics