Optimization of impulse resistance reduction for tower grounding device of transmission line

Journal of Physics: Conference Series(2020)

Cited 0|Views0
No score
Abstract
Abstract When the lightning strikes the tower, the lightning current is discharged into the ground through the tower grounding device. The magnitude of the impulse earthed resistance of the tower grounding device determines the lightning discharge capacity of the tower. Therefore, the tower grounding device directly affects the lightning protection level of the tower. This paper first introduces three commonly used shock resistance reduction methods: long vertical ground electrode, acupuncture ground electrode, and externally induced rays. Then, the CDEGS software is used to simulate and analyze the long vertical grounding electrode, and a method of insulation short shield is proposed to determine the optimal length of the vertical grounding conductor of the grounding device. Finally, the different resistance reduction effects under the change of length and number of roots are explored, and the optimal resistance reduction arrangement under the same economic conditions is realized.