Performance Insulator Cover Type : YSL-70-AP Post Voltage Break Down Test

Logic : Jurnal Rancang Bangun dan Teknologi(2020)

引用 0|浏览0
暂无评分
摘要
Electrical energy affect to economic, electrical energyconsumption will increase and decrease likely economics. In this globalization era, electricity consumption was increased trendyearly since industrialization era. The reliability Electrical energy is very importantfor economic growth. The lower SAIDI and SAIFI is the bench mark for reliability of electrical energy supply. The reliable of insulator cover type: YSL-70-AP affect to the reliability electrical distribution energy on over head distribution circuit. Insulator cover protected to over head distribution circuit againt animal, bird, tree ang other temporarydisturbance. Insulator cover also to protect half insulated medium voltage cable againtpartial discharge and flashover. Over voltage stress more often during operation, to impact to the material insulationperformance.This quantitative research founding: insulator cover type: YSL-70-AP still feasible to use after voltage breakdown stress. The fault current is still under the maximum allowable leakage current (11,600 micro ampere) which is 41.61 micro ampere, and breakdown voltage is still higher than minimum that specified (24 kilo volt), which is 49.63 kilo volt.Post breakdown voltage the material insulation performance of insulator cover type: YSL-70-APis good, and reliable to continuous operation over head distribution circuit.
更多
查看译文
关键词
cover,breakdown,performance
AI 理解论文
溯源树
样例
生成溯源树,研究论文发展脉络
Chat Paper
正在生成论文摘要