Analysis of Deterioration Characteristics for Connection Factor used in Grounding System

Hyoung-Jun Gil,Kil-Mok Shong,Young-Seok Kim, Chong-Min Kim

Journal of the Korean Society of Safety(2015)

Cited 0|Views1
No score
Abstract
This paper describes the analysis of deterioration characteristics for connection factor used in grounding system. The connection method of grounding system is specified in IEC standard. In order to analyze the deterioration characteristics for connection factor, deterioration test was carried out when the connection factor was buried in salt water and underground. The test connection factors were C-type sleeve, clamp, and exothermic welding. As a consequence, most of the connection factor was corroded, and the electrical resistance decreased after deterioration. The analytical results can be used to establish the safety of grounding system.
More
Translated text
Key words
connection factor,deterioration characteristics