Reducing the energy consumption of a variable air volume (VAV) system in heating, ventilation, and air-conditioning (HVAC) systems attracts many attentions. In this letter, a novel method, namely, optimal dynamic duct static pressure (ODSP) method is proposed to find the globally optimal solutions of the original non-convex multi-zone VAV system energy optimization problem. Our method is based on the primal dual interior point method to solve an equivalent convex optimization problem of the multi-zone VAV system energy optimization problem. Different from existing methods, our method is a real-time optimization method and explicitly considers the duct network model to find the energy saving strategy. Numerical simulations illustrate the effectiveness of our method compared with current methods, which show that our method provides better energy efficiency and nearly 20% energy is saved. Our method also has the guarantee to find the optimal solutions.
More
Translated text
Key words
Fans, Ducts, Shock absorbers, Optimization, Energy consumption, Buildings, Resistance, Damper position, optimal control, multi-zone variable air volume system, energy saving