本文对某电厂发电机励磁机烧损导致机组停机的事故进行了分析,认为发电机转子导电杆与励磁机整流环之间的连接的铜排接触不良,发热后导致导电杆相间绝缘损坏发生短路起火,是导致事故的原因,并对此问题提出了预防措施.