一起330kV变电站跳闸事故原因分析

Qinghai Electric Power(2016)

Cited 0|Views11
No score
Abstract
介绍一起330 kV变电站保护误动事故,通过技术分析及现场试验,指出故障合并单元FPGA芯片短暂工作异常引起插值时刻出错,装置输出波形畸变导致事故发生,并提出建议,以避免相同事故再次发生.