一起重合闸误动导致的遥控操作失败分析

Jiangxi Electric Power(2017)

Cited 0|Views10
No score
Abstract
本文围绕某220 kV线路遥控操作时所发生的遥控操作失败故障的分析及处理过程,结合遥控操作原理及影响遥控因素,从故障现象入手,剖析了遥控操作失败的原因,定位为由于保护开入回路端子松动导致遥控操作时重合闸出口,从而导致断路器重合,最后提出了针对性的建议.