冲击接地电阻测量新方法及应用

Popular Utilization of Electricity(2015)

Cited 0|Views3
No score
Abstract
梅州地处山区,属于雷害高发区,每年因雷击造成的输电线路跳闸占线路总跳闸数的80%以上 通过分析发现,雷击跳闸主要集中在某些杆塔.经测量,这些杆塔的工频接地电阻均满足规程要求,但输电线路在运行时,仍经常发生雷害.笔者后来通过查阅相关资料,发现频繁遭受雷击与杆塔的冲击接地电阻有很大关系.经测量,这些杆塔的冲击电阻偏大,达不到防雷要求.通过使用化学降阻剂、延伸接地网等措施后,冲击接地电阻减少,达到了规程要求,相关杆塔多年来再没有发生过雷害.