Cooling Capacity and Energy Performance of Open-Type Ceiling Radiant Cooling Panel System with Air Circulators

Mi-Su Shin, Ji-Su Choi, Kyu-Nam Rhee

ENERGIES(2021)

引用 7|浏览0
暂无评分
摘要
Ceiling radiant cooling panel (CRCP) systems are being increasingly applied to commercial buildings due to their high thermal comfort level and energy efficiency. It is recommended that CRCP systems should be operated at a relatively high chilled water temperature to prevent condensation and save energy. However, even though a high chilled water temperature is effective for achieving condensation-free operation and high chiller efficiency, it can lead to insufficient cooling capacity. In this study, a method of enhancing the cooling capacity of CRCP systems was investigated through mock-up chamber tests. The open-type installation of CRCPs and the combination of air circulators were used to enhance the cooling capacity and energy performance of CRCP systems. Experimental results showed that compared to a conventional CRCP system, the cooling capacity of an open-type CRCP system with air circulators increased by up to 26.2%, and its cooling energy consumption decreased by up to 26.4%. Additionally, the open-type CRCP system with air circulators reduced the difference between the room air temperature and mean chilled water temperature. Thus, the proposed system can operate at a relatively high chilled water temperature, which is effective for reducing condensation risk and cooling energy consumption.
更多
查看译文
关键词
ceiling radiant cooling panel,cooling capacity,open-type installation,air circulators,cooling energy consumption