An air curtain is used to ensure an adequate separation between two compartments that is aimed to restrict, a clean one and a contaminated one. The air curtain performance is improved with the use of an air extraction from the "contaminated" compartment. The aerodynamic sealing of an optimized air curtain is assessed regarding particulate matter. The evaluation using visual assessment of the aerodynamic sealing using a cold smoke source is validated against PM 10 detection.It is shown that the air curtain presents a good aerodynamic sealing for the particulate of PM10 and PM2.5 classes and that the visual assessment method can lead to similar results. An equation was obtained with a view to be used to predict the level of aerodynamic sealing of the air curtain when the exhaust rate becomes too low. Another equation was obtained for predicting the average velocity through the door protected by the air curtain required to obtain an aerodynamic sealing, as a function of the jet parameters (nozzle average velocity and thickness). These test results prove that the air curtain, complemented with an air exhaust from the "contaminated compartment", is suitable to provide an acceptable aerodynamic sealing for the particulate matter.
更多
查看译文
关键词
Airborne bacteria, plane jets, full size experiments, vertical air curtains