Analysis Of The Coupling Between The Outer And Inner Control Loops Of A Grid-Forming Voltage Source Converter

2020 22ND EUROPEAN CONFERENCE ON POWER ELECTRONICS AND APPLICATIONS (EPE'20 ECCE EUROPE)(2020)

Cited 7|Views26
No score
Abstract
The question of grid forming control is very different depending on the connection to a low voltage or high voltage grid. In case of higher power application, the low switching frequency may induce some stability issues. This question has been studied and some solutions have been proposed through new inner current and voltage control tuning methods. However, the possible interactions between the inner and the outer controls have not been discussed yet. Actually, in large power system, the phasor modeling approximation is used in order to ease the analysis and reduce the time computations. It assumes a good decoupling between the control loops, which allows neglecting the inner loop dynamics. This paper investigates the effectiveness of this assumption by taking some examples of tuning methods proposed in the literature and showing the ability of each method to guarantee the decoupling between controllers. In this paper, small-signal analysis tool, participation factors and parametric sensitivities are used.
More
Translated text
Key words
Grid-forming based voltage source converter, State-Space modeling, Small-signal analysis, Participation factors, Parametric sensitivities