Ageing state identification and analysis of AC 500 kV XLPE submarine cable based on high-voltage frequency dielectric response

IET Science, Measurement & Technology(2020)

Cited 15|Views20
No score
Abstract
Carrying out the insulation condition measurement and analysis is important for the safe operation of the submarine cable. In this study, the high-voltage frequency dielectric response is used to identify the ageing state of the AC 500 kV cross-linked polyethylene (XLPE) submarine cable. The complex capacitance and tan δ in the low-frequency area for the new, thermal ageing, electro-thermal ageing cable all increase with the testing voltage increased from 200 to 2000 V. It is founded that the dielectric response at high voltage is more likely to detect the ageing differences. Based on the carbonyl index and the dielectric loss of the XLPE specimens at different position of the insulation layer, the non-uniform ageing phenomenon of the cable insulation is presented for the thermal ageing and electro-thermal ageing cable. The loss quantity parameter and its changing behaviour with testing voltage based on the frequency dielectric response could be used to identify the ageing state. The comparison of the modified Cole–Cole model parameter under 200 and 2000 V also indicates that the higher voltage dielectric response is helpful to identify the ageing differences.
More
Translated text
Key words
permittivity,submarine cables,ageing,XLPE insulation,power cable insulation,dielectric losses,power cable testing,insulation testing
AI Read Science
Must-Reading Tree
Example
Generate MRT to find the research sequence of this paper
Chat Paper
Summary is being generated by the instructions you defined