Parametric analysis of the thermal behavior of a single-channel solar chimney

SOLAR ENERGY(2020)

引用 19|浏览4
暂无评分
摘要
This work presents the design, construction, instrumentation and thermal evaluation of a single-channel solar chimney under a warm-humid climate. A solar chimney (0.8 m width and 2 m length) with a capacity for varying the air gap (0-0.28 m), the inclination angle (0 - 90 degrees), and the amount of energy absorbed by the absorber plate. A parametric study was performed with a total of 60 tests under laboratory conditions. A maximum temperature difference of 16.7 degrees C was obtained for an angle of 15 degrees and a 0.075 m air gap, and when the air gap was varied, the highest air speed was 0.38 m s(-1). The results show that a solar chimney can be used as a passive ventilation system, where up to 5 times more air flow can be removed in an enclosure, with a maximum air change rate (ACH) of 27.11 h(-1), and a maximum efficiency of 88.9%. The data obtained can be used not only to select the configuration of a chimney but also for other applications where heating or the removal of air is required, such as for drying or in ventilated roofs.
更多
查看译文
关键词
Solar chimney,ACH,Single channel,Thermal evaluation,Ventilation system