Influence of electrical joint compound on the temperature rise of electrical equipment

PROCEEDINGS OF THE 3RD INTERNATIONAL CONFERENCE ON ADVANCES IN ENERGY AND ENVIRONMENTAL SCIENCE 2015(2015)

引用 0|浏览6
暂无评分
摘要
Electrical joint compound is widely used in metal connections of high-voltage electrical equipment. Based on studying a defect of electrical equipment connection fittings, the influence of electrical joint compound on the temperature rise of electrical equipment was studied according laboratory experiment and field test. It was found that, when the contact resistance of two aluminun achieved to 441 mu Omega, the temperature rise shows centered in partial heat generation. Therefore, it is recommended to strengthen the quality control on the electrical joint compound, reduce temperature rise defective of electrical equipment.
更多
查看译文
关键词
electrical joint compound,contact resistance,temperature rise,electrical equipment