In the present work, a new electrothermal combined stress test cell has been designed and fabricated to conduct accelerated electrothermal ageing. The fabricated test cell includes all possible real working conditions of the transformers. The effects of accelerated electrothermal ageing on the performance of power transformers with thermally upgraded Kraft (TUK), Nomex-910 and Nomex-410 solid dielectrics in conjunction with mineral oil have been investigated. The accelerated electrothermal ageing has been performed for a temperature range of 100 degrees C to 220 degrees C, along with 10 kV electrical stress. Subsequently, several electrical, thermal, mechanical and chemical properties of transformer oil and different paper dielectrics have been determined. It has been observed from the diagnostic test results that Nomex impregnated mineral oil samples have better electrothermal performance as well as oxidation stability when compared to the thermally upgraded Kraft oil samples. Therefore, Nomex insulating materials in conjunction with mineral oil are suggested as alternative solid dielectrics for power transformers in order to achieve better oxidation stability, improved thermal performance for long service runs and reduced operating and maintenance costs. It is envisioned that the present experimental study will be very beneficial to utility managers and end-users of power transformers.