Experimental and numerical study on formation of interface separation and interfacial dielectric strength of GIL insulator

IEEE Transactions on Dielectrics and Electrical Insulation(2019)

引用 25|浏览7
暂无评分
摘要
As the transmission capacity of gas insulated transmission line (GIL) increases, the synergistic improvement in dielectric and mechanical strengths of GIL insulators is urgently needed for the development of advanced power systems. Mechanical defects in power equipment are prone to induce discharges during high voltage operations, which need to be mitigated. In this paper, the strains on the GIL insulator surface are measured by fiber Bragg grating (FBG) strain sensors during hydrostatic tests. An abnormal change of strain is detected near the interface between center conductor and the spacer. The numerical results of stress distributions of GIL insulator during manufacturing and high-voltage operation are calculated by the finite element method. The results indicate that the mechanical stresses are concentrated at the interface, which lead to the development of conductor-spacer interface separation. In addition, based on the hydrostatic test and the FEM calculations, the dielectric interfacial strength, including the electric field distribution, and flashover are investigated by a combination of numerical and experimental studies. The results indicate that the air gaps generated by the separated interface distort the electric field at the tip of the gap, which is likely to cause discharges and reduce the gas-solid interfacial flashover strength of the insulator, placing concerns of insulation failure and even operating failures of GIL. This work sheds light on the importance of interfacial structure of power equipment and will guide the design and the manufacture of GIL insulator.
更多
查看译文
关键词
GIL insulator,fiber Bragg grating,stress concentration,interface separation,interfacial dielectric strength
AI 理解论文
溯源树
样例
生成溯源树,研究论文发展脉络
Chat Paper
正在生成论文摘要