A Comparative Study of the Oil-Free Centrifugal Water Chillers with the Flooded or Falling Film Evaporator—A Case Study

Kuo-Shu Hung, Jenn-Chyi Chung,Chung-Che Liu, Jun-Jie Lin,Chi-Chuan Wang

ENERGIES(2019)

Cited 0|Views1
No score
Abstract
A comparative study regarding the performance of real-scale oil-free centrifugal chillers having the flooded evaporator or falling film evaporator was conducted in this study. The nominal capacity for the test chillers was around 200 similar to 230 USRT (US refrigeration ton) (703 similar to 809 kW). The compressors of the two chillers were identical and R-134a was used as the working fluid. Both evaporators employed the same enhanced tubes (GEWA-B) to fulfill phase change. Tests were conducted in full, 75%, 50%, and 25% loading. Test results indicate that both chillers contained a comparable system performance with an integrated part-load value of around 8.62 similar to 8.63. The overall heat transfer coefficient for the flooded evaporator was appreciably higher (20 similar to 40%) than the falling film evaporator. This is because the falling film flowrate was below the threshold value and the heat transfer was dominated by evaporation mode. Yet, the heat transfer performance for the falling film evaporator was further jeopardized due to starvation of the film flowrate (partial dry-out), especially in the middle or bottom of the tube bundle. This phenomenon became even more pronounced at partial loading (25%), whereas the flooded evaporator did not reveal such a performance dip at partial loading.
More
Translated text
Key words
oil-free centrifugal chiller,flooded evaporator,falling film evaporator,heat transfer
AI Read Science
Must-Reading Tree
Example
Generate MRT to find the research sequence of this paper
Chat Paper
Summary is being generated by the instructions you defined