Feasibility study and performance evaluation of low capacity water–LiBr absorption cooling systems functioning in different Algerian climate zones

International Journal of Refrigeration(2017)

引用 14|浏览6
暂无评分
摘要
•Water–LiBr absorption chillers were analysed in the five climate zones in Algeria.•In zones E1 and E2, the chillers produced chilled water at 7 °C and partial charge.•In the hot zones E3, E4 and E5, it was not feasible to produce chilled water at 7 °C.•The chillers were able to produce chilled water at 12 °C in zones E3 and E4.•The chillers were not able to operate under the thermal conditions of zone E5.
更多
查看译文
关键词
Thermal cooling,Absorption chillers,Water–LiBr,Climate zones in Algeria