Diagnostic potential of free-space radiometric partial discharge measurements
2017 XXXIInd General Assembly and Scientific Symposium of the International Union of Radio Science (URSI GASS)(2017)
摘要
The work reported in this paper addresses the calibration of four types of partial discharge (PD) emulator required for the development of a PD Wireless Sensor Network (WSN). Three partial discharge (PD) emulators have been constructed: a floating-electrode emulator, and two internal PD emulators. Both DC and AC HV power supplies are used to initiate PD which is measured using concurrent free-space radiometry (FSR) and a galvanic contact method based on the IEC 60270 standard. A new method of estimating absolute PD activity level from a radiometric measurement is proposed.
更多查看译文
关键词
IEC 60270 standard,galvanic contact method,PD wireless sensor network,radiometric measurement,absolute PD activity level,concurrent free-space radiometry,internal PD emulators,floating-electrode emulator,partial discharge emulator,free-space radiometric partial discharge measurements,diagnostic potential