Calculation of the pressure rise caused by internal arc faults in HV metal-enclosed SF6 GIS

2016 IEEE International Power Modulator and High Voltage Conference (IPMHVC)(2016)

引用 0|浏览2
暂无评分
摘要
High reliability of HV SF 6 switchgear makes an internal arc fault an extremely rare event. However, its occurrence cannot be completely avoided, and therefore must be considered in the design process. Internal arc testing in SF 6 is not recommended due to its harmful environmental impact, but if necessary, tests should be performed only inside special containers, that will prevent the release of SF 6 into the atmosphere. Having in mind that tests in SF 6 and air are not yet fully comparable, accurate modeling of pressure rise due to internal arc faults is still the main means to evaluate required design parameters of SF 6 switchgear in respect of safety from internal arc faults. A simulation tool, which calculates the pressure rise due to an internal arc inside a metal-enclosed SF 6 compartment, was developed and used in the design of a new HV GIS. The calculation procedure and obtained results were described and discussed. Validation of the tool was performed using experimental data from SF 6 internal arc tests, dating back several decades ago, when internal arc tests in SF 6 were not questionable as today.
更多
查看译文
关键词
HV GIS (high-voltage gas-insulated switchgear),SF6 gas,internal arc,pressure rise,gas compartment,bursting disc,enclosure burn-through