System simulation for an untreated sewage source heat pump (USSHP) in winter

Proceedings of SPIE(2017)

引用 0|浏览9
暂无评分
摘要
The paper discusses the system characteristics of an untreated sewage source heat pump in winter. In this system, the sewage enters into the evaporator directly. The variable parameters to control the system contain the sewage temperature at evaporator inlet and the water temperature at condenser inlet. It is found that most parameters, except the condensation heat transfer coefficient, change in the form of sine wave the same as the sewage temperature at inlet. The heating load and consumed power are 12.9kW and 3.45kW when the sewage temperature at inlet is 13.. COP is about 3.75 in the range of the sewage temperature at inlet of 12-13 degrees C.
更多
查看译文
关键词
untreated sewage source heat pump,direct mode,sewage inlet temperature