Chrome Extension
WeChat Mini Program
Use on ChatGLM

A Study on the Signal Analysis of Corona Discharge on the Polymer Insulator using UV Sensor Array

Journal of The Korean Institute of Illuminating and Electrical Installation Engineers(2014)

Cited 0|Views2
No score
Abstract
To prevent any accident in electric power utilities, many researches for inspection and diagnosis deteriorations occurring by corona discharges have been continuously studying. Inspection and diagnosis of electric power utility is very important to prevent an accident. This paper studies a measurement of ultra-violet(UV) ray of corona discharges on polymer insulators using an UV sensor array with an optic lens. The detection of an UV signal begins at 60kV, which is about 37.5% of the breakdown voltage of the polymer insulator and the stronger the high voltage increased to the polymer insulator was. It can be determined that the polymer insulator mounted on a live part must be examined when the discharge risk exceeds approximately 40%. In conclusion, the status of power utilities can be checked using an UV sensor.
More
Translated text
Key words
corona discharge
AI Read Science
Must-Reading Tree
Example
Generate MRT to find the research sequence of this paper
Chat Paper
Summary is being generated by the instructions you defined