Contacts Impact Phenomena In A 126 Kv Vacuum Circuit Breaker

25TH INTERNATIONAL SYMPOSIUM ON DISCHARGES AND ELECTRICAL INSULATION IN VACUUM (ISDEIV 2012)(2012)

引用 8|浏览6
暂无评分
摘要
The contacts closing impact phenomenon of vacuum interrupter is a basic event in a vacuum circuit breaker, which reveals lots of information including impact force, bouncing duration, stress distribution and so on. The objective of this paper is to investigate the contacts impact phenomenon in a 126 kV vacuum circuit breakers. PVDF (polyvinyldene fluoride) piezoelectric sensors were used to measure impact force of a 126 kV vacuum circuit breaker at a closing velocity of 1.5 m/s. In addition, a finite element analysis simulation model of contacts impact in a 126 kV vacuum interrupters was set up by using ANSYS / LS-DYNA software. The experimental results showed that the maximum contacts impact force of a 126 kV vacuum circuit breaker was about 10(5) N at 1.5 m/s closing velocity, which is are in good agreement with the simulation results. And the simulation results also showed that the maximum impact force, durations of contact bounce and the maximum stresses of contact were related with some parameters of vacuum interrupter, such as contact shape, elastic modulus of contact material, impact velocity and contact spring force.
更多
查看译文
关键词
electrical contacts,elastic moduli,finite element analysis
AI 理解论文
溯源树
样例
生成溯源树,研究论文发展脉络
Chat Paper
正在生成论文摘要