The merits of open bath immersion cooling of datacom equipment

Santa Clara, CA(2010)

引用 70|浏览5
暂无评分
摘要
This paper discusses the economic and environmental merits of passive 2-phase immersion in semi-open baths of dielectric fluid for cooling datacom equipment such as servers. The technique eliminates the need for hermetic connectors, pressure vessels, seals and clamshells typically associated with immersion cooling and the connectors, plumping, pumps and cold plates associated with more traditional liquid cooling techniques. A board level power density of 11.7W/cm2 can be sustained with 100 cm3 of fluid per kW. The modular 80 kW baths modeled can eject 130 kW per m2 of floor space via water-cooled condensers. It is estimated that 28°C water at 15 gpm could maintain average CPU junction temperatures, Tj<;60°C and 62°C water at 30 gpm could maintain Tj<;85°C, maximizing the availability of the heat for other purposes. Alternatively, the heat can be transferred directly to ambient air without water as an intermediate. The costs and greenhouse gas emissions associated with conservative annual fluid emission estimates are found to be less than those associated with the electrical power required for traditional chassis fans and liquid pumps. Since these fugitive losses occur at one point, more efficient capture techniques can be easily applied.
更多
查看译文
关键词
cooling,data communication equipment,heat exchangers,datacom equipment,dielectric fluid,evaporative bath,fluoroketone,open bath immersion cooling,water-cooled condensers,2-phase,data center,datacenter,datacom,immersion,open bath,passive,pressure vessel,fluids,servers,assembly,heat transfer,electric power,power density,greenhouse gas emissions,heating
AI 理解论文
溯源树
样例
生成溯源树,研究论文发展脉络
Chat Paper
正在生成论文摘要