“2.24”事故对福建省风电并网管理的启示

Electric Power and Electrical Engineering(2011)

Cited 2|Views7
No score
Abstract
以西北电网"2.24"风电大规模脱网事故为典型案例,详细分析了事故原因,指出风电场不接地系统的保护跳闸方式不合理、低电压穿越能力不足、无功补偿设备功能不完善等问题是导致此次事故的主要原因。最后借鉴事故的经验教训,结合福建省风电并网现状,提出对该省风电并网管理的若干建议。