Faulty Feeder Detection and Fault Self-Extinguishing by Adaptive Petersen Coil Control

Power Delivery, IEEE Transactions(2011)

Cited 52|Views4
No score
Abstract
The characteristic of the single-phase earth fault in the Peterse coil grounded distribution network is discussed in this paper. It is disclosed that only the derivative of the zero-sequence current of the faulty feeder changes with the controllable inductance of the Petersen coil, while the derivative of the zero-sequence current of the sound feeder is kept invariable. Therefore, a novel faulty feeder selection criterion is proposed. A variety of simulation tests is carried out. The exactness and sensitivity of the proposed scheme are verified by simulation test results.
More
Translated text
Key words
coils,resonant grounding,power distribution faults,faulty feeder detection,adaptive petersen coil,self-extinguish,power distribution protection,maximum current derivative,sound feeder,residual current,earthing,adaptive petersen coil control,fault location,zero-sequence current,fault self-extinguishing,coil grounded distribution network,adaptive control,voltage,capacitance,inductance,earth,indexing terms,fault detection,resonance,zero sequence current