SPD残压测量回路中差模干扰问题

Insulators and Surge Arresters(2008)

Cited 23|Views48
No score
Abstract
为了解决限压型SPD残压测量波形严重畸变上凸、幅值偏大的现象,进行了理论计算、EMTP-ATP程序仿真、新旧同轴电缆对比试验和人为将新电缆屏蔽层末端强行接地的试验,结果表明:相同引线长度,相同8/20冲击电流幅值情况下,理论计算、EMTP-ATP程序仿真、新电缆屏蔽层不接地测量残压波形符合要求,引线在SPD上端电压降(U′AB)等于引线在SPD下端的(UAB);人为将新电缆屏蔽层末端强行接地或破损同轴电缆呈现SPD残压波形严重变形上凸,冲击电流幅值越大,上凸越严重,引线在SPD上端时的电压降(U′AB)大于下端的(UAB),且均大于新电缆屏蔽层不接地的测量结果。新电缆屏蔽层接地或破损电缆构成两端接地测量系统,两端接地点存在电位差,通过阻性耦合产生电磁干扰,在同轴电缆屏蔽层和大地之间产生共模干扰电压,芯线和屏蔽层之间产生差模干扰电压。
More
Translated text
Key words
the residual voltage,surge current,SPD,ATP-EMTP,differential mode interference