750kV扩径导线的运行情况总结

Electric Power Construction(2007)

Cited 6|Views30
No score
Abstract
我国750kV输变电示范工程线路全长140.705km,其中使用了24.462km的扩径导线。输电线路使用扩径导线,直接投资有所降低,但运行中损耗增加。如果750kV线路载流较小,可以考虑使用扩径导线,较大时不宜采用扩径导线。展放扩径导线时发生了跳股现象,发生跳股的原因是导线通过滑轮时发生跳股的股线受到了两侧导线的挤压。经过1年多的运行,扩径导线没有发生明显变化。
More
Translated text
Key words
750 kV line,oversized conductor,strand jump,operation summary,economic analysis