Pressure Drop Of Two-Phase Helium Flowing In A Large Solenoidal Magnet Cooling Path And A Long Transfer Line

T. Haruyama,O. Araoka,Y. Doi,K. Kasami, Y. Makida,S. Suzuki, K. Tanaka, A. Yamamoto

CRYOGENICS(1996)

引用 4|浏览4
暂无评分
摘要
The pressure drop of two-phase helium flowing in a 64 m cooling path of a magnet and a 58 m connecting transfer line was investigated. A large thin superconducting solenoidal magnet, which was developed for the SDC detector (Solenoidal Detector Collaboration for the former SSC project), was used for this experiment. The magnet is 3.8 m in diameter, 2 m in length with a total cold mass of 4.5 tons. It was cooled by two-phase helium flow passing through a serpentine cooling path. The pressure drops of single-phase gas helium flow during cool down and two-phase helium flow in steady cooling were measured and compared with predictions. The measured pressure drop of single-phase helium agreed well with the prediction; however, the measured pressure drop of two-phase helium was much larger than the predictions based on separated and homogeneous flow models. In the high mass-flow region of two-phase flow, slight pressure oscillations were observed in the inlet, outlet and differential pressures of the magnet. The magnet temperature was stable and not affected by those oscillations.
更多
查看译文
关键词
two-phase helium, pressure drop, magnet cooling